This Test set is suitable to measure winding resistance of transformers, single or 3-phase, star or delta connected upto several MVA.Two independent displays read the resistance of both primary & secondary windings simultaneously. However, primary or secondary winding can also be measured separately.
DC Power source allows the selected current to flow through the winding /windings and the voltage developed across the winding are sent to instrumentation amplifiers, thereby displaying directly the ohmic value.
Technical Features:
| Resistance Range | Resistance meter reading display | Resolution | Test Current TypeUONT005A | Test Current TypeUONT010A |
| 2mW | 19.99×0.1 | 1mW | 5A | 10A |
| 20mW | 19.99×1 | 10mW | 5A | 10A |
| 20mW | 199.9×0.1 | 10mW | 500mA | 1A |
| 200mW | 199.9×1 | 100mW | 500mA | 1A |
| 0.200W | 1999×0.1 | 100mW | 50mA | 100mA |
| 2W | 1999×1 | 1mW | 50mA | 100mA |
| 2W | 19.99×0.1 | 1mW | 5mA | 10mA |
| 20W | 19.99×1 | 10mW | 5mA | 10mA |
| 20W | 199.9×0.1 | 10mW | 0.5mA | 1mA |
| 200W | 199.9×1 | 100mW | 0.5mA | 1mA |
| 200W | 1999×0.1 | 100mW | 0.05mA | 0.1mA |
| 2KW | 1999×1 | 1W | 0.05mA | 0.1mA |
Input Power Supply: 230V +10%, single phase, 50Hz. AC.
Accuracy: +1% of selected resistance range.
Display: 2 nos., 31/2 digit LED module for resistance measurement.
Protection:
- Protection against current lead disconnection while in use, Induction Kickback suppression, Snap acting overload protection.