TYPE: CBANT01
SYSTEM FEATURES:
- 80386 or higher microprocessor based system.
- Solid state data storage capacity.
- Data is stored in MS Windows readable format.
- Data can be exchanged by normal floppy.
- Analyzing software can be run on any normal PC with the captured data.
- Any dot matrix or inkjet printer can give output graphs on any paper.
- Multiple operating observations are captured by the machine and kept in the memory.
- LCD Screen Display.
DATA ACQUISITION FEATURES:
- 100 kHz A/D conversion.
- All channels are optically isolated.
- 0.5 ms sampling interval per channel.
The operations will be for single break in OFFLINE mode. MAKE, BREAK and O-C-O sequence operation will be provided.
Parameters RECORDABLE:
- Total Travel.
- Contact Gap.
- Contact Loading/Erosion Clearance.
- Contact Penetration.
- Closing Bounce.
- Opening Rebounce.
- Opening and Closing time.
- Speed and Travel at various specified transit positions.
- Transient opening and closing coil voltage.
- Transient opening and closing coil current.
DIGITAL DATA CHANNELS AVAILABLE:
- R phase Contact
- Y phase Contact
- B phase Contact
- N – Contact.
- R phase Contact – 1
- R phase Contact – 2
- Y phase Contact – 1
- Y phase Contact – 2
- B phase Contact – 1
- B phase Contact – 2
- N – Travel
- Closing coil voltage
- R Closing Coil Current
- Y Closing Coil Current
- B Closing Coil Current
- N Closing Coil Current
Analogue Date Channels
Marked channels are normally required and as per our current plan further channel can be extended with the software change only.
SPECIFICATION:
Timing : A period of 100ms nominal.
Trigger : Closure of external voltage free contact to start calibration.
Power Supply: 230 V, 1 Ph, 50Hz.,AC.