DOUBLE FREQUENCY DOUBLE VOLTAGE TEST SET

SKU: 45b92cd18a82 Category:

This test set provides a continuously variable output voltage at double frequency to test the insulation between turns of coils, layer to layer, terminals of windings with either uniform or graded insulation and also between the windings and earth, with graded insulation of both Distribution and Power transformers.
An alternating voltage of sine wave form (as much as possible) at double frequency (100 Hz.) and double in amplitude can be applied at one side of the transformer under test while the windings, which are not connected to the source of excitation, are left on open circuit. This higher frequency is considered to avoid excessive excitation current during the testing.

Voltage source:

To generate a voltage at 100 Hz., one 3-phase squirrel cage induction motor is given a supply through a star-delta switch. This motor drives the slip ring induction motor (generator). A variable voltage is also supplied to the generator thereby producing double frequency, which along with the output voltage of the generator is available across the terminals of the Set.

Selection chart:

Type

Output capacity of generator(slip-ring motor)

In HP

Output capacity of generator(slip-ring motor)

In kW

Suitable to test transformer upto
dfdv010h10HP7.5KW250KVA
dfdv020h20HP15 KW750KVA
dfdv025h25HP18.75KW1MVA
dfdv030h30HP22.5KW2MVA
dfdv040h40HP30KW3MVA
dfdv050h50HP37.5KW4MVA

dfdv060h

60HP45KW5MVA
dfdv080h80HP60KW6MVA
dfdv100H100HP75KW7.5MVA
dfdv150h150HP112.5KW11.2MVA