?IBL? make Oil Test Set is ideal for testing of Breakdown/withstand test of transformer and circuit breaker oil, in accordance with IS 6792:1992 for oil testing.
Input: 230V + 10%, 50Hz., 1 phase AC.
Selection chart:
| Mode of operation | Type | Maximum output(In kV) with center point of H.V.winding grounded |
| Manually operated | OTMN050S OTMN060S OTMN070S OTMN075S OTMN080S OTMN090S OTMN100S OTMN120S |
50 60 70 75 80 90 100 120 |
|
Motor operated |
OTMT050S OTMT060S OTMT070S OTMT075S OTMT080S OTMT090S OTMT100S OTMT120S |
50 60 70 75 80 90 100 120 |
| Microcontroller/Microprocessor based Fully Automatic | OTAU050S OTAU060S OTAU070S OTAU075S OTAU080S OTAU090S OTAU100S OTAU120S |
50 60 70 75 80 90 100 120 |
Capacity: 10mA in the HT side for all sets.
Transformer: H.V. Transformer used in the Test set is cast resin type of graded insulation with center point of H.V. winding grounded.
Protection: Zero start interlocking & door-interlock is to be provided. Snap acting automatic tripping of H.V. circuit in case of overload or breakdown of oil sample under test.
Overvoltage indication (audio & visual) is also incorporated.
Metering: Analog meter for manually & motor operated sets. Digital display for automatic sets.
Test Vessel: As per IS 6792:1992. A gauge is provided along with the cell to adjust the gap.
Features that can be provided at extra cost for manually & motor operated sets:
Capacity other than standard setting, Digital Metering, Stirring arrangement, Mushroom electrode, Cylindrical electrode.