TRANSFORMER WINDING RESISTANCE METER

SKU: 0034bc78e983 Category:

This Test set is suitable to measure winding resistance of transformers, single or 3-phase, star or delta connected upto several MVA.Two independent displays read the resistance of both primary & secondary windings simultaneously. However, primary or secondary winding can also be measured separately.
DC Power source allows the selected current to flow through the winding /windings and the voltage developed across the winding are sent to instrumentation amplifiers, thereby displaying directly the ohmic value.

Technical Features:

Resistance RangeResistance meter reading displayResolution

Test Current

TypeUONT005A

Test Current

TypeUONT010A

2mW19.99×0.11mW5A10A
20mW19.99×110mW5A10A
20mW199.9×0.110mW500mA1A
200mW199.9×1100mW500mA1A
0.200W1999×0.1100mW50mA100mA
2W1999×11mW50mA100mA
2W19.99×0.11mW5mA10mA
20W19.99×110mW5mA10mA
20W199.9×0.110mW0.5mA1mA
200W199.9×1100mW0.5mA1mA
200W1999×0.1100mW0.05mA0.1mA
2KW1999×11W0.05mA0.1mA

Input Power Supply: 230V +10%, single phase, 50Hz. AC.
Accuracy: +1% of selected resistance range.
Display: 2 nos., 31/2 digit LED module for resistance measurement.

Protection:

  • Protection against current lead disconnection while in use, Induction Kickback suppression, Snap acting overload protection.